Current Carrying Capacity of Copper Wire Per sq mm
| Nominal CrossSection (mm²) | 0,75 | 1,5 | 1 | 6 | 16 | 10 | 25 | 4 | 2,5 | 35 | |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Group 1 | Protective Fuse(A) | 10 | 6 | 25 | 50 | 32 | 63 | 20 | 16 | 80 | |
| Current Carrying Capacity(A) Copper Wire | 15 | 11 | 33 | 61 | 45 | 83 | 25 | 20 | 103 | ||
| Group 3 | Protective Fuse(A) | 10 | 20 | 16 | 50 | 80 | 63 | 100 | 32 | 25 | 125 |
| Current Carrying Capacity(A) Copper Wire | 15 | 24 | 19 | 54 | 98 | 73 | 129 | 42 | 32 | 158 | |
| Group 2 | Protective Fuse(A) | 6 | 16 | 10 | 32 | 63 | 50 | 80 | 25 | 20 | 100 |
| Current Carrying Capacity(A) Copper Wire | 12 | 18 | 15 | 44 | 82 | 61 | 108 | 34 | 26 | 135 | |
| Nominal CrossSection (mm²) | 50 | 150 | 120 | 185 | 95 | 70 | 240 | 400 | 300 | 500 | |
| Group 1 | Protective Fuse(A) | 100 | 200 | 160 | 125 | ||||||
| Current Carrying Capacity(A) Copper Wire | 132 | 235 | 197 | 165 | |||||||
| Group 3 | Protective Fuse(A) | 160 | 315 | 315 | 400 | 250 | 200 | 400 | 630 | 500 | 630 |
| Current Carrying Capacity(A) Copper Wire | 198 | 391 | 344 | 448 | 292 | 245 | 528 | 726 | 608 | 830 | |
| Group 2 | Protective Fuse(A) | 125 | 250 | 250 | 315 | 200 | 160 | 315 | 400 | ||
| Current Carrying Capacity(A) Copper Wire | 168 | 335 | 292 | 382 | 250 | 207 | 453 | 504 | |||
Copper Wire Ampacity Chart
| Copper (Wire Size and Amp Ratings) | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Wire Gauge Size | 14 | 10 | 12 | 1 | 8 | 1/0 | 3/0 | 4 | 2/0 | 6 | ||
| 60°C (140°F) | NM-B, UF-B | 15 | 30 | 20 | — | 40 | — | — | 70 | — | 55 | |
| 75°C (167°F) | THW, THWN, | SE, USE, XHHW | 20 | 35 | 25 | 130 | 50 | 150 | 200 | 85 | 175 | 65 |
| 90°C (194°F) | THWN-2, THHN, | XHHW-2, USE-2 | 25 | 40 | 30 | 145 | 55 | 170 | 225 | 95 | 195 | 75 |
| Copper (Wire Size & Amp Ratings) | ||||||||||||
| Wire Gauge Size | 3 | 4/0 | 2 | 300 | 250 | 750 | 350 | 600 | 1000 | 500 | ||
| 60°C (140°F) | NM-B, UF-B | 85 | — | 95 | — | — | — | — | — | — | — | |
| 75°C (167°F) | THW, THWN, | SE, USE, XHHW | 100 | 230 | 115 | 285 | 255 | 475 | 310 | 420 | 545 | 380 |
| 90°C (194°F) | THWN-2, THHN, | XHHW-2, USE-2 | 115 | 260 | 130 | 320 | 290 | 535 | 350 | 475 | 615 | 430 |
| Check Above Copper Wire AMP Chart Before Buying the Products | ||||||||||||
Annealed Bare Copper Wire Specification
Bundled Conductors Derating Factors
| Bundle# | 2/5 | 7/15 | 16-30 |
|---|---|---|---|
| Derating Factor (X Amps) | 0.8 | 0.7 | 0.5 |
Cu Wire Diameter and Properties
| No of wires | 7 | 7 | 7 | 7 | 7 | 7 | 10 | 7 | 7 | |
|---|---|---|---|---|---|---|---|---|---|---|
| Nom cross sectional area (mm²) | 16 | 1.5 | 25 | 35 | 10 | 2.5 | 50 | 6 | 4 | |
| Dia of conductors (mm) | 4.8 | 1.59 | 5.8 | 6.9 | 3.85 | 2.01 | 8.2 | 3.15 | 2.55 | |
| Dia of wires (mm) | 1.74 | 0.53 | 2.19 | 2.62 | 1.35 | 0.67 | 2.62 | 1.05 | 0.85 | |
| Mech prop of plain copper wire | Min Elongation% | 28 | 24 | 28 | 28 | 26 | 24 | 28 | 26 | 24 |
| Min TensileStrength(N/mm2) | 200 | 200 | 200 | 200 | 200 | 200 | 200 | 200 | 200 | |
| Max Dcresistance at 20°(ohms/km) | 1.15 | 12.1 | 0.727 | 0.524 | 1.83 | 7.41 | 0.387 | 3.08 | 4.61 | |
| Nom weight (kg/km) | 137 | 13 | 215 | 300 | 87 | 21 | 410 | 52 | 35 | |
| No of wires | 14 | 48 | 19 | 19 | 61 | 37 | 37 | 61 | 61 | |
| Nom cross sectional area (mm²) | 70 | 240 | 95 | 120 | 300 | 185 | 150 | 500 | 400 | |
| Dia of conductors (mm) | 9.7 | 18.6 | 11.4 | 13.1 | 20.4 | 15.8 | 14.2 | 30 | 26 | |
| Dia of wires (mm) | 2.62 | 2.62 | 2.62 | 2.62 | 2.62 | 2.62 | 2.62 | 3 | 3 | |
| Mech prop of plain copper wire | Min Elongation% | 28 | 28 | 28 | 28 | 28 | 28 | 28 | 33 | 33 |
| Min TensileStrength(N/mm2) | 200 | 200 | 200 | 200 | 200 | 200 | 200 | 200 | 200 | |
| Max Dcresistance at 20°(ohms/km) | 0.268 | 0.0754 | 0.193 | 0.153 | 0.0601 | 0.0991 | 0.124 | 0.0366 | 0.047 | |
| Nom weight (kg/km) | 595 | 2100 | 820 | 1040 | 2700 | 1600 | 1280 | 4400 | 3400 | |
Amperes Conductor Chart
| Insulation Materials: | Polyethylene(High Density) | Polyvinylchloride PVC (Irradiated) Nylon | Neoprene Polyurethane Polyethylene Polyvinylchloride (Semi-Rigid) |
Kapton FEP PTFE PFA Silicone |
Kynar (135°C) Polyethylene(Crosslinked) Thermoplastic Elastomers |
|---|---|---|---|---|---|
| Copper Temp. | 90°C | 105°C | 80°C | 200°C | 125°C |
| 28 AWG | 4 | 4 | 3 | 6 | 5 |
| 30 AWG | 3 | 3 | 2 | 4 | 3 |
| 26 AWG | 5 | 5 | 4 | 7 | 6 |
| 22 AWG | 9 | 10 | 8 | 13 | 11 |
| 24 AWG | 7 | 7 | 6 | 10 | 8 |
| 20 AWG | 12 | 13 | 10 | 17 | 14 |
| 16 AWG | 22 | 24 | 19 | 32 | 26 |
| 18 AWG | 17 | 18 | 15 | 24 | 20 |
| 14 AWG | 30 | 33 | 27 | 45 | 40 |
| 10 AWG | 55 | 58 | 47 | 75 | 70 |
| 12 AWG | 40 | 45 | 36 | 55 | 50 |
| 8 AWG | 70 | 75 | 65 | 100 | 90 |
| 4 AWG | 135 | 145 | 125 | 180 | 170 |
| 6 AWG | 100 | 105 | 95 | 135 | 125 |
| 2 AWG | 180 | 200 | 170 | 240 | 225 |
Copper Cable Density
| Condition | Standard Conditions | High-Temperature Applications |
|---|---|---|
| Current Density | 1 to 1.5 A/mm² | Up to 2 A/mm² or more |
| Description | Typical range for general applications. | Can be higher depending on cooling and insulation. |
Copper Conductor Resistance Table
| Nom cross section | 0,05 | 0,14 | 0,126 | 0,08 | 0,34 | 0,22 | 0,5 | 6,0 | 1,0 | 16,0 | 10,0 | 1,5 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Cu conductor-tinned wires (Ohm/km) | ~380 | ~134 | ~150 | 237 | 39,0 | 99 | 26,0 | 3,30 | 19,5 | 1,21 | 1,91 | 12,2 |
| Copper conductor-plain wires (Ohm/km) | – | – | – | – | 36,0 | 96 | 24,5 | 3,08 | 18,1 | 1,15 | 1,83 | 12,1 |
| Welding cable (Ohm/km) | ~392 | ~138 | ~175 | ~244 | 40,1 | 76 | 26,7 | 3,11 | 20,0 | 1,24 | 1,95 | 13,7 |
| Cu conductor (tinned wires) | – | – | – | – | – | – | – | – | – | 1,19 | – | – |
| Copper conductor (plain wires) | – | – | – | – | – | – | – | – | – | 1,16 | – | – |
| Nom cross section | 2,5 | 25,0 | 4,0 | 35,0 | 70,0 | 50,0 | 120,0 | 300,0 | 150,0 | 500,0 | 400,0 | 630,0 |
| Cu conductor-tinned wires (Ohm/km) | 7,98 | 0,386 | 4,95 | 0,272 | 0,161 | 0,206 | 0,129 | 0,0641 | 0,0801 | 0,0396 | 0,0486 | 0,0286 |
| Copper conductor-plain wires (Ohm/km) | 7,41 | 0,387 | 4,61 | 0,268 | 0,153 | 0,193 | 0,124 | 0,0601 | 0,0754 | 0,0366 | 0,0470 | 0,0283 |
| Welding cable (Ohm/km) | 8,21 | 0,393 | 5,09 | 0,277 | 0,164 | 0,195 | 0,126 | 0,0607 | 0,0762 | – | 0,0475 | 0,0292 |
| Cu conductor (tinned wires) | – | 0,390 | – | 0,276 | 0,159 | 0,204 | 0,105 | – | – | – | – | – |
| Copper conductor (plain wires) | – | 0,379 | – | 0,268 | 0,155 | – | 0,125 | 0,0654 | 0,0817 | – | – | – |
Copper Wire Current Carrying Capacity Formula
I = k × Ab
Where,
Copper Conductor Applications
Copper Cable Current Carrying Capacity Types
35 sq mm Copper Cable
| Capacity | Transmission | Applications | Durability | Compliance | Voltage Drop | Safety | Power |
|---|---|---|---|---|---|---|---|
|
|
|
|
|
|
|
|
10 sq mm Wire Current Capacity
6 sq mm Wire
| Conductivity and Durability | Cabling Needs | Current Handling Capacity | Cost Efficiency | Performance |
|---|---|---|---|---|
|
|
|
|
|
70 sq mm Cable Current Capacity
| Current Carrying Capacity | Common Use | Design | Heat Resistance | Performance |
|---|---|---|---|---|
|
|
|
|
|
120 sq mm cable current carrying capacity
| Feature | Versatile Use | Reliability | Current Carrying Capacity | Long-Distance Performance | Efficiency | |
|---|---|---|---|---|---|---|
| Details |
|
|
|
|
|
|
95 sq mm cable current capacity
16 sq mm copper cable current carrying capacity
1 sq mm wire current capacity
| Current Carrying Capacity | Corrosion Resistance | Versatile Use | High Tolerance | Cost-Effective |
|---|---|---|---|---|
|
|
|
|
|
1.5 sq mm wire
185 sq mm cable current capacity
| Current Carrying Capacity | Tensile Strength | Safety and Convenience | High Performance | Mechanical Strength |
|---|---|---|---|---|
|
|
|
|
|
240 sq mm aluminium cable current carrying capacity
| Current Capacity | Versatility | Applications | Safety and Efficiency |
|---|---|---|---|
|
|
|
|
How does the current affect the required size of a conductor?
Aluminium Cable Current Carrying Capacity
| 4.0 Sq MM Cable Details | ||||
|---|---|---|---|---|
| Guage | Volts Support | Load | Amp | Suitable For |
| 4.0 Sq MM | 250 | 800 Watts | 110 | Normal Load |
| 2.5 Sq MM Cable Specification | ||||
| Guage | Volts Support | Load | Amp | Suitable For |
| 2.5 Sq MM | 250 | 500 Watts | 110 | Normal Load |
| 6.0 Sq MM Cable Specification | ||||
| Guage | Volts Support | Load | Amp | Suitable For |
| 6.0 Sq MM | 250 | 1200 Watts | 110 | Normal Load |
| 10 Sq MM Cable Load Specification | ||||
| Guage | Volts Support | Load | Amp | Suitable For |
| 10 Sq MM | 250 | 2500 Watt | 110 | Heavy Load |
| 8.0 Sq MM Cable Load Capacity | ||||
| Guage | Volts Support | Load | Amp | Suitable For |
| 8.0 Sq MM | 250 | 1800 Watt | 110 | Heavy Load |
Copper Conductor vs Aluminum Conductor
| Features | Copper Conductor | Aluminum Conductor |
|---|---|---|
| Conductivity |
|
|
| Weight |
|
|
| Strength |
|
|
| Corrosion Resistance |
|
|
| Flexibility |
|
|
| Applications |
|
|
| Thermal Expansion |
|
|
| Electrical Resistance |
|
|